Figure 59. Dv/Dt Filter Cabinet In Sc9000 Ep Lineup; Figure 60. Dv/Dt Filter Power Flow - Eaton SC9000 EP Installation Manual

Medium voltage drives
Table of Contents

Advertisement

Figures 59 and 60 show the dV/dt filter cabinet location and
power flow position in the SC9000 EP.

Figure 59. dV/dt filter cabinet in SC9000 EP lineup

Figure 60. dV/dt filter power flow

dV/dt cooling requirements
The installed filter's cabinet cooling system provides its
required cooling. This system consists of an inlet air filter and
outlet air fan, located in the cabinet door, and an air outlet
vent on top of the control cabinet. The filter and fan require
periodic maintenance for maximum efficiency.
Maintenance
Inspect the dV/dt filter cabinet cooling system periodically to
assure maximum uptime and effectiveness. Inspect the
cooling fan and inlet air filter at least once every three
months. Clean the filters with an air jet and dust the fan to
prevent dust buildup in the fan motor and bearings. Replace
the fan every three to five years.
SC9000 EP medium voltage drives IB020001EN—February 2016 www.eaton.com
Appendix D: Optional equipment
65

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sc9000 gpSc9000 ep ar

Table of Contents