Figure 58. Dv/Dt Representative Cabinet Outlines; Table 13. 2300 V Dv/Dt Filters; Table 14. 4160 V Dv/Dt Filters - Eaton SC9000 EP Installation Manual

Medium voltage drives
Table of Contents

Advertisement

Appendix D: Optional equipment
SC9000 EP dV/dt filters and ratings
SC9000 EP dV/dt Filter designs are based upon drive rated
voltage and current. Eaton application engineers select a
filter during the project design process. Tables 13 and 14
show SC9000 EP dV/dt filter models.

Table 13. 2300 V dV/dt filters

Catalog
Drive
number
power
39C2078
(hp)
G43
300
G44
400
G45
500
G46
600
G48
800
G410
1000
G412
1250
G415
1500
G420
2000
G425
2500

Table 14. 4160 V dV/dt filters

Catalog
Drive
number
power
39C2028
(hp)
G43
300
G44
400
G45
500
G46
600
G48
800
G410
1000
G412
1250
G415
1500
G420
2000
G425
2500
G430
3000
G435
3500
G442
4250
G450
5000
G460
6000
64
SC9000 EP medium voltage drives IB020001EN—February 2016 www.eaton.com
Filter
Cabinet
rating
size
(A)
(H x W x D)
71
92 x 24 x 50
93
92 x 24 x 50
116
92 x 24 x 50
136
92 x 36 x 50
180
92 x 36 x 50
225
92 x 36 x 50
279
92 x 36 x 50
335
92 x 36 x 50
446
92 x 36 x 50
558
92 x 36 x 50
Filter
Cabinet
rating
size
(A)
(H x W x D)
44.7
92 x 24 x 50
57.0
92 x 24 x 50
65.1
92 x 24 x 50
81.5
92 x 36 x 50
101
92 x 36 x 50
125
92 x 36 x 50
159
92 x 36 x 50
186
92 x 36 x 50
248
92 x 36 x 50
310
92 x 36 x 50
373
92 x 40 x 50
434
92 x 40 x 50
527
92 x 40 x 50
633
92 x 40 x 50
760
92 x 40 x 50
dV/dt filter as part of the SC9000 EP lineup
During the project application and design process, the
intended cable lengths and motor type selected will
determine whether to apply a dV/dt filter. If your project
needs a dV/dt filter, Eaton application engineers will select
a filter for the intended drive, motor and installation.
Physical location in SC9000 EP drive
Watts
The SC9000 EP dV/dt filter, when present, is typically located
loss
in the SC9000 EP panel lineup, adjacent to and downstream
(W)
of the inverter cabinet. However, it can be located remotely
1024
depending on the application and installation constraints.
1084
1102
Filter cabinet outline
1383
Figure 58 shows a typical cabinet outline for a dV/dt filter.
1440
1514
1658

Figure 58. dV/dt representative cabinet outlines

1802
2129
2226
Watts
loss
(W)
1282
1360
1357
1674
2029
2011
2163
3348
3444
3592
4843
4632
6731
7892
8033