Figure 3. Frame C, Frame D, And Frame E Transformer Section Overhead Lifting - Eaton SC9000 EP Installation Manual

Medium voltage drives
Table of Contents

Advertisement

Figure 3. Frame C, Frame D, and Frame E transformer section overhead lifting

A
B
Front view
A and B Dimensions
Unit
A Dimension
Frame C converter
34.75 inches
Frame D converter
40.5 inches
Frame E converter
50 inches
Spreader bar
Remove cover plates
front and rear to
insert lifting channels
B Dimension
65 inches
76 inches
100 inches
SC9000 EP medium voltage drives IB020001EN—February 2016 www.eaton.com
Chapter 4: Handling, storage, and installation
Top view
15