o i
menu
X5200 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
1) Consecutive uv o i Fails
2) Consecutive ir o i Fails
3) o i Calibrate Active
4) uv o i Cal Flt
5) ir o i Cal Flt
6) manual o i Active
7) manual uv o i Flt
8) manual ir o i Flt
3.2
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
Allowable number of consecutive UV o i failures to produce a fault. Factory set
to three (minutes). This is the time between fault occurrence and annunciation.
Allowable number of consecutive IR o i failures to produce a fault. Factory set
to three (minutes). This is the time between fault occurrence and annunciation
o i calibration is in progress.
UV o i calibration has detected a fault condition.
IR o i calibration has detected a fault condition.
A manual o i test is in progress.
Manual UV o i fault. Check UV viewing window and o i reflector plate
cleanliness.
Manual IR o i fault. Check IR viewing window and o i reflector plate
cleanliness.
Status Info Menu
1) Warm Up (Y/N)
2) Fire (Y/N)
3) UV Alarm (Y/N)
4) IR Alarm (Y/N)
5) TDSA Alarm (Y/N)
6) Quick Alarm (Y/N)
7) UV Pre Alarm (Y/N)
8) IR Pre Alarm (Y/N)
9) Auto UV Oi Fault (Y/N)
10) Auto IR Oi Fault (Y/N)
11) Manual Oi at Start
12) Sensor Hdwr. Fault (Y/N)
13) HIB Hardware Fault (Y/N)
14) Internal Com. Fault (Y/N)
15) Incompatible Fault (Y/N)
16) Voltage Fault (Y/N)
17) Hardware Menu
18) Oi Menu
12
Oi Menu
1) Consecutive UV Oi Fails
2) Consecutive IR Oi Fails
3) Oi Calibrate Active
4) UV Oi Cal Flt
5) IR Oi Cal Flt
6) Manual Oi Active
7) Manual UV Oi Flt
8) Manual IR Oi Flt
95-8636
Need help?
Do you have a question about the X5200 and is the answer not in the manual?
Questions and answers