9.7 Overload Protection

Troubleshooting
Electronic
Thermal
External fault A
contact input
External fault B
contact input
Operating
method when
the frequency
command is
lost
Remote
keypad
communication
error
EEP: Parameter save error
HWT: Hardware fault
Err: Communication error
COM: Keypad error
NTC: NTC error
IOLT : IOLT(inverter Overload Trip) protection is activated at 150% of the inverter
rated current for 1 minute and greater.
OLT : OLT is selected when F56 is set to 1 and activated at 200% of F57[Motor rated
current] for 60 sec in F58. This can be programmable.
Table 9.2 – Corrective Actions
Motor has
overheated.
Load is greater than
inverter rating.
ETH level is set too
low.
Drive capacity is
incorrectly selected.
The terminal set to "18
(External fault-A)" or
"19 (External fault-B)"
in t1-t8 within terminal.
No frequency
command is applied to
V1 and I.
Communication error
between drive keypad
and remote keypad.
Reduce load and/or
duty cycle.
Change drive with
higher capacity.
Adjust ETH level to an
appropriate level.
Select correct drive
capacity.
Eliminate the cause of
fault in the circuit
connected to external
fault terminal.
Check the wiring of V1
and I and frequency
reference level.
Check for connection
of communication line
and connector.
Call Baldor-Reliance
for assistance.
9-9