Baldor VS1MD User Manual page 101

Table of Contents

Advertisement

7-56
1 = Operation stops when cooling fan malfunctions
When cooling fan fault occurs,
LED and operation is stopped. If t32 and/or t33 is set to 17 (Fault Output),
fault message is displayed.
H81 -
Second Motor Parameters
H90
Range:
Default:
Access
See Also:
These parameters activate when a selected terminal is ON and one of the
t1 thru t8 terminals is set for 12 (2
Param.
Description
H81
Accel Time
H82
Decel Time
H83
Base Freq
H84
V/F Pattern
H85
FX Torque Boost
H86
RX Torque Boost
H87
Stall Level
H88
1 Min Overload Level
H89
Continuous Overload Level
H90
Motor Rated Current
Use these settings when an inverter operates two motors connected to two
different types of loads. 2
the same time. When first selected motor operation is stopped, select a
terminal for the second motor and define H81 thru H90 to run the second
motor.
Sets the V/F pattern for the second motor.
See below
See below
Configurable
t1-t8
nd
Motor Select).
Range
0 ~ 60000 Sec
0 ~ 60000 Sec
30 ~ 400 Hz
0 ~ 2
0 ~ 15 %
0 ~ 15 %
30 ~ 150 %
50 ~ 200 %
50 ~ 150 %
0.1 ~ 50 Amps
nd
motor operation does not drive two motors at
VS1MD
P8
message is displayed on the
Factory Default
Adj. run
1.0
5.0
60.0
0
5
5
150
150
100
26.3
M 1
M 2
VS1MD AC Drive User Manual
-
-
-
-
-
-