Baldor VS1MD User Manual page 76

Table of Contents

Advertisement

Parameter Descriptions
F14
Time for magnetizing a motor
Range:
Default:
Access
See Also:
This parameter accelerates the motor after pre-exciting the motor for the set
time. The amount of the pre-exciting current is set in H34 – Motor no load
current.
F20
Jog Frequency
Range:
Default:
Access
See Also:
This parameter sets the Jog Frequency, it cannot be set above P36 –
Frequency High Limit. Jog is only available in 2-wire control mode.
F27
Torque Boost select
Range:
Default:
Access
See Also:
If F27 = 0, set manual torque boost values in F28 and F29.
torque boost
torque boost
FX
RX
If F27 = 1 (Auto toque boost), the inverter automatically calculates torque
boost values using motor parameters and outputs the corresponding
voltage. Before enabling Auto torque boost, H34 – No load current and H42
– Stator resistance must be set properly.
0-60 [sec]
0.1
Configurable
P30, P32, H32, H34, H40, H42, H44
0-400 [Hz]
10.00
Tunable
P36, t1-t8
0=Manual Torque Boost
1=Auto Torque Boost
0
Configurable
F28-F29, H34, H41-42
Voltage
100%
F28 - FX
F29 - RX
No torque boost
Time
7-31