Parameter Read/Write - Baldor VS1MD User Manual

Table of Contents

Advertisement

8.9
8.9.1
8-18
The following table shows the fault type while this function is active.
No.
Display
1
UPHF
Switch above IGBT's U phase fault
2
UPLF
Switch below IGBT's U phase fault
3
vPHF
Switch above IGBT's V phase fault
4
vPLF
Switch below IGBT's V phase fault
5
WPHF
Switch above IGBT's W phase fault
6
WPLF
Switch below IGBT's U phase fault
7
UWSF
Output short between U and W
8
vUSF
Output short between U and V
9
WvSF
Output short between V and W
10
UPGF
Ground fault at U phase
11
vPGF
Ground fault at V phase
12
WPGF
Ground fault at W phase
13
UPOF
Output open at U phase
14
vPOF
Output open at V phase
15
WPOF
Output open at W phase

Parameter Read/Write

Group
Display
H91
Function
group 2
H92
Used to read/write Inverter Parameters using remote keypad.
!
Parameter Read
Step 1. Move to H91 code.
Step 2. Press Enter ( ) key once. 0 will be displayed.
Step 3. Press Up ( ) key once. Rd will be displayed.
Step 4. Press Enter ( ) key twice. Rd will be displayed
Step 5. H91 is displayed when Parameter read is finished.
Fault type
Parameter Name
[Parameter Read]
[Parameter Write]
ATTENTION: Take caution when Parameter write (H92) is
executed. By doing this, parameters in inverter are cleared
and parameters in remote keypad are copied to inverter.
Diagnosis
Contact sales representatives.
Check for a short in inverter output
terminal, motor connection
terminal or the proper motor
connection.
Check for ground fault occurring at
inverter output cable or motor or
motor insulation damage.
Check for proper connection of the
motor to the inverter output or
proper motor connection.
Setting
Range
1
0 to 1
1
0 to 1
VS1-MD AC Drive User Manual
Default
Unit
0
0