Parameter Descriptions
t35
Criteria for Analog Input Signal Loss
Range:
Default:
Access
See Also:
Selects the drive mode when frequency reference set by the Analog (V1, I)
input terminal or communication option is lost.
t35
[Criteria for analog input
signal loss]
Example 1) The inverter determines the freq reference is lost when P40 –
Freq set method is set to 3 (Analog V1 input), t16 to 1 and analog input
signal is less than half the value set in t36.
Example 2)The inverter determines the freq reference is lost when P40 –
Freq set method is set to 6 (V1+I), t16 to 2 and V1 input signal is either
below the value set in t36 or I input value is less than the t46 value.
Example diagram when t35 is set to 2, I62 to 2, I63 to 5.0 sec and t32 to 11:
6 H W
I U H T
U H T
0 2
5 X Q
F R P P D Q G
t36
Analog Input 0 to -10V (NV) Min voltage
Range:
Default:
Access
See Also:
Sets the minimum voltage of the NV (-10 to 0V) input.
0 = Disabled
1 = Activated below half of set value
2 = Activated below set value
0
Tunable
t32-t33, t36, t41, t46, t62-t63
0
1
2
0 to -10V
0
Tunable
P40, t37
Disabled (Does not check the
analog input signal loss)
When half the value set in t36,
t41, t46 is entered
When less than the value set in
t36, t41, t46 is entered
 V H F
7-21