Baldor VS1MD User Manual page 108

Table of Contents

Advertisement

8.1.4 Frequency Setting via 0 to 20 [mA] Input
8.1.5 Frequency Setting via -10 to +10 V „ Voltage Input + 0 to 20 mA „
Customizing for Your Application
Group
Code
P37
[Frequency Command]
Drive
group
P40
[Frequency Setting Method]
t45
[Filter Time Constant for I Input]
t46
[I Input Minimum Current]
I/O
t47
[Frequency Corresponding to I12]
group
t48
[I input Max Current]
t49
[Frequency Corresponding to I14]
Step 1. Set P40 [Frequency Setting Method] to "4".
Step 2. Frequency is set via 0 to 20mA input between I and CM terminal.
Input
Group
Code
P37
[Frequency Command]
Drive
group
P40
[Frequency Setting Method]
Step 1. Set P40 [Frequency Setting Method] to "5".
Step 2. Override function available using Main/Auxiliary speed adjustment
Step 3. Related code: t36, t39, t40, t44, t45, t49
Override function allows more precise control and a faster response by combining
Main and Auxiliary speed input. Fast response can be achieved via Main speed and
precise control can be accomplished by Aux. speed if the accuracy of Main/Aux speed
is set differently.
Follow the settings shown in the table below when Main speed is given via 0 to 20mA
with Aux. speed via V1 terminal (–10 to 10V).
Parameter Name
Parameter Name
-
5
Setting
Range
Initial
-
0 to 400
0.00
4
1 to 7
1
10
0 to 9999
10
-
0 to 20
4
-
0 to 400
0.00
-
0 to 20
20
-
0 to 400
60.00
Setting
Range
Initial
0 to 400
0.00
1 to 7
1
Unit
Hz
mA
Hz
mA
Hz
Unit
Hz
8-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents