Siemens Apogee P1 Technical Manual

Communications interface
Hide thumbs Also See for Apogee P1:

Advertisement

Quick Links

Siemens Apogee P1
Communications
Interface
Technical Manual
HA470909 Issue 1
Compatible with Version 1.x Software
 Copyright Eurotherm Drives Limited 2003
All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or
by any means to persons not employed by a Eurotherm Drives company without written permission from Eurotherm
Drives Ltd.
Although every effort has been taken to ensure the accuracy of this document it may be necessary, without notice, to
make amendments or correct omissions. Eurotherm Drives cannot accept responsibility for damage, injury, or expenses
resulting therefrom.
E U R O T H E R M
D R I V E S

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Apogee P1

  • Page 1 E U R O T H E R M D R I V E S Siemens Apogee P1 Communications Interface Technical Manual HA470909 Issue 1 Compatible with Version 1.x Software  Copyright Eurotherm Drives Limited 2003 All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or by any means to persons not employed by a Eurotherm Drives company without written permission from Eurotherm Drives Ltd.
  • Page 2 Safety Information Please read this information BEFORE installing the equipment. Intended Users This manual is to be made available to all persons who are required to install, configure or service equipment described herein, or any other associated operation. The information given is intended to highlight safety issues, and to enable the user to obtain maximum benefit from the equipment.
  • Page 3: Table Of Contents

    POGEE ECHNOLOGY PTION A System Overview................... 1 Protocol ........................1 Product Features ......................1 Size Notation – Part Numbers..................1 Installation ....................... 2 Apogee P1 FLN Communication Module (HVAC10) ............2 • PLC/SCADA Supervisor (4-wire only)............2 • Cable Specification..................2 • Cable Routing ....................2 •...
  • Page 5: Pogee

    PTION A System Overview The Apogee P1 Technology Option provides a serial data port, allowing VSDs (variable speed drives) to be linked to form a network. Using a PLC/SCADA or other intelligent device, this network can be continuously controlled to provide supervision and monitoring for each VSD in the system.
  • Page 6: Installation

    Wait 5 minutes after disconnecting power before working on any part of the system or removing the covers from the Drive. Apogee P1 FLN Communication Module (HVAC10) You can create a network of drives by linking a Master (PLC or Apogee controller) to one or more HVAC10 drives fitted with this module.
  • Page 7: User Connections To The Main Serial Port (P1)

    User Connections to the Main Serial Port (P1) The serial port on the Option allows the following Apogee P1 links to be made. RS485 RS485 RS485 RS485 Electrical Connections 4-wire 2-wire differential differential Number of transmitters and transceivers 32 drivers...
  • Page 8: Terminal Block (Tb1) Connections

    Option. On the SIZE 1 unit it will protrude slightly above the standard plastic enclosure. • Make all user wiring connections. Refer to the Wiring Diagrams. • Re-fit the terminal cover securely with the screws. Siemens Apogee P1 Communications Interface...
  • Page 9: Wiring Diagrams

    PLC/SCADA (master) TRANSMIT RECEIVE TRANSMIT RECEIVE RECEIVE TRANSMIT 0V SCR RXB RXA TXB TXA TXB TXA 0V SCR RXB RXA Figure 4 4-Wire Wiring Diagram for the HVAC10 Size 2 & 3 Drive Siemens Apogee P1 Communications Interface...
  • Page 10 PLC/SCADA (master) TRANSMIT RECEIVE TRANSMIT RECEIVE RECEIVE TRANSMIT TXB TXA 0V SCR RXB RXA TXB TXA 0V SCR RXB RXA Figure 6 4-Wire Wiring Diagram for the HVAC10 Size 1 Drive Siemens Apogee P1 Communications Interface...
  • Page 11: Initial Check For Connection

    FAULT Parameter Indication Description Description Description Description SELF TEST Initialising SHORT FLASH HARDWARE Hardware fault FLASH TYPE MISMATCH Wrong type or disabled LONG FLASH PARAMETER Set-up fault, parameter values out-of-range NONE Valid set-up, ready for external communications Siemens Apogee P1 Communications Interface...
  • Page 12 SOFT TIMEOUT: Drive not addressed in the last 10 seconds. OK: Device has been addressed. Note: The NETWORK LED can only be in the ON state when the MODULE LED is ON continuously, indicating that the Option is ready for external communications. Siemens Apogee P1 Communications Interface...
  • Page 13: Initial Set-Up For Apogee P1

    Using the Operator Station (MMI) or other suitable PC programming tool, the TEC OPTION MMI Menu Map function block requires configuring before the Apogee P1 option can be used. Non-specific MMI view The parameter names/functions in the TEC OPTION function block are inter-dependant and will 1 SETUP change with different parameter values and the various Technology Options that can be fitted.
  • Page 14 5 : DISABLED Serial communication has been disabled (default) Also refer to Network LED, page 8. NIGHT Range: FALSE/TRUE Shows the Night occupancy set by the FLN P1 network. Siemens Apogee P1 Communications Interface...
  • Page 15: Troubleshooting

    Check that switch SW1:1 is ON, i.e. selected for 2- wire operation. Check power for all equipment on the network, e.g. RS232 to RS485 converter or repeater. SOFT TIMEOUT: Check the PLC/SCADA program is running. Drive not addressed in the last 10 seconds. Siemens Apogee P1 Communications Interface...
  • Page 16: Point Database For Siemens Apogee P1

    Point Database for Siemens Apogee P1 Point Point Subpoint Name Factory Default Engr. Units Slope Intercept On Text Off Text Number Type (SI Units) (SI Units) (SI Units) (SI Units) CTRL ADDRESS – – – ED_HVAC10 – – – Error! Reference Freq Output –...
  • Page 17 Point Database for Siemens Apogee P1 cont. Analog 1 Out 0.01 -163.83 – – Analog 2 Out 0.01 -163.83 – – Analog 3 Out 0.01 -163.83 – – Analog In 1 0.01 -163.83 – – Analog In 2 0.01 -163.83 –...
  • Page 18: Point Database Cross Reference

    Setup/Motor Control/Flycatching/Enable Flycatching Setup/Motor Control/Flycatching/Active Analog 1 Out Setup/Inputs & Outputs/An Out/An Out 1/Value Analog 2 Out Setup/Inputs & Outputs/An Out/An Out 2/Value Analog 3 Out Setup/Inputs & Outputs/An Out/An Out 3/Value continued on next page… Siemens Apogee P1 Communications Interface...
  • Page 19 Skip Freq 4 Startup/Setpoint Funcs/Skip Frequencies/Freq 4 Band 4 Startup/Setpoint Funcs/Skip Frequencies/Band 4 AR Enable Setup/Seq & Ref/Auto Restart/Enable AR attempts Setup/Seq & Ref/Auto Restart/Attempts AR Delay Setup/Seq & Ref/Auto Restart/Attempt Delay 1 Error Status Siemens Apogee P1 Communications Interface...
  • Page 20 ISS. MODIFICATION ECN No. DATE DRAWN CHK'D First release of HA470909. 16656 16/04/03 FIRST USED ON MODIFICATION RECORD Siemens Apogee P1 Communications Interface DRAWING NUMBER SHT. 1 EUROTHERM DRIVES ZZ470909 OF 1...

Table of Contents