DT4220 E
Function
Sequence of operations 1. Enter the menu by typing the supervisor code.
20180619-V0
7.15. Menu item 16: Analog output signal setting
In this menu item you can choose between 4-20 mA and
0-20 mA output current.
[Factory default: 4-20 mA]
The analog output can indicate the error state too. When the error
occurs the analog signal changes to 3.2 mA or 22 mA. (selectable)
2. Keep stepping by pressing the ▲ button as long as you see this
menu item.
3. Enter the menu item by pressing the Menu button.
4. Pressing the ▲ button, select the desired sub-menu item.
5. You can enter to sub-menu by pressing the Menu button and you
can exit from sub-menu item by pressing the Esc button.
(6. Press Esc button again if you want to leave the menu.)
The selectable sub-menus:
analog output type
4-20 or 0-20 mA.
analog output error
3.2 or 22 mA.