Setting The Operating Mode - Datcon DT4220 E Series Operating Instructions Manual

Process indicator
Table of Contents

Advertisement

Function
Sequence of operations Read the chapter 7.1. Functions of the push-buttons during
40

7.13.1. Setting the operating mode

Here you can define the operating mode of limit output.
[Factory default: OFF]
navigation in the menu for learning the buttons handle.
1. Enter the menu by typing the supervisor code.
2. Keep stepping by pressing the ▲ button as long as you see this
menu item.
3. Enter the menu item by pressing the Menu button.
4. Pressing the ▲ button, select the desired value.
5. Exit from menu item by pressing the Esc button. The change is
saved to FRAM.
(6. Press Esc button again if you want to leave the menu.)
The selectable values:
 off:
The output is always in switched off condition.
 high:
The output gets switched on, when the displayed physical value is
higher than or equal with the low limit value.
 low:
The output gets switched on, when the displayed physical value is
lower than the low limit value.
 inside:
The output gets switched on, when the displayed physical value is
between the low limit value and the high limit value.
 outside:
The output gets switched on, when the displayed physical value isn't
between the low limit value and the high limit value.
 heating:
The output gets switched on, when the displayed physical value is
lower than the low limit value. The output gets switched off, when the
displayed physical value is higher than the high limit value.
 cooling:
The output gets switched on, when the displayed physical value is
higher than the high limit value. The output gets switched off, when
the displayed physical value is lower than the low limit value.
 on:
The output is switched on independently from the measured value.
DT4220 E
20180619-V0