6. Setting up

6.1. Zeroing

The DT7000 is calibrated according to the measuring range
given on the data label.
However a small zero offset may occur caused by the shock
under shipping or mounting. This can be trim by
potentiometers.
The following figure shows the position of the
potentiometers:
With potentiometer 1. (P32) you can zero the output current
(zero point 4 mA or 12 mA).
With potentiometer 4. (P62) you can zero the display value.
Do not set span potentiometers (2. (P31), 3. (P63)).