Emc-Compliant Installation - Lenze i510 protec Mounting And Switch-On Instructions

Table of Contents

Advertisement

EMC-compliant installation

The drive system (inverter and drive) only complies with the EMC Directive 2014/30/EU if it is installed
according to the guidelines for CE-typical drive systems.
These guidelines should also be followed in installations requiring FCC Part 15 or ICES 001 compliance.
NOTICE
Electromagnetic interferences
Product and peripheral devices may be affected during operation.
▶ Use integrated conductive shield connections for control lines and motor lines.
▶ Use central earthing points.
These inverters do not have an integrated RFI filter in the AC mains supply.
In order to meet the EMC requirements according to EN 61800−3, an external EMC filter according
to IEC EN 60939 must be used.
The user must verify that the conformity with EN 61800−3 is fulfilled.
The following example shows the effective wiring:
A
Shield connection for control connections
B
Control line
C
EMC cable gland
EMC-compliant installation must be implemented with shielded motor cables of low capacitance.
Capacitance per unit length:
• C-core-core/C-core-shielding: < 75/150 pF/m ≤ 2.5 mm² (≥ AWG 14);
• C-core-core/C-core-shielding: < 150/300 pF/m ≥ 4 mm² (≤ AWG 12)
A
B
C
D
E
D
Motor cable with low capacity
E
Power line
Electrical installation
EMC-compliant installation
21

Advertisement

Table of Contents
loading

Table of Contents