Digital Interface Settings - Bosch Rexroth CytroPac Operating Instructions Manual

Hydraulic power unit
Hide thumbs Also See for Rexroth CytroPac:
Table of Contents

Advertisement

Table 6: Modification of approved parameters
Code
Name
E0.26
Acceleration time
E0.27
Delay time
F1.03
Pressure command value, source
F1.05
Pressure command value 0
F1.06
Pressure command value 1
F1.07
Pressure command value 2
F1.08
Pressure command value 3
F1.11
Flow command value, source
F1.12
Flow command value
F2.19
Function input X4
F2.20
Function input X5
F3.12
Proportional amplification, p/Q controller
F3.13
Integral time, p/Q controller
F3.16
Differential amplification, p/Q controller
F3.17
Filter time for differential amplification
F4.45
Boost for pressure drop compensation
H3.20
Station name (PROFINET)

8.3.1 Digital interface settings

Changing the operating pressure:
Make sure that all system components can work with the required operating
pressure.
Make sure that the pressure limitation settings for the intended operating
pressure are correct (10 % over max. operating pressure).
The pressure command value can also be changed during running operation.
Command values entered in the software become immediately effective in the
process!
Pressure command value change (applies for "Basic" and "Advanced" configurations):
1.
Make sure that parameter F1.03 is set to 0.
2.
Set the required operating pressure in parameter F1.05.
Change of up to four pressure ratings (applies for "Basic" and "Advanced"
configurations):
1.
Make sure that parameter F1.03 is set to 1 (parameter F1.04 indicates the status
of the pre-selected pressure).
2.
Set the required operating pressure for stage 1 in parameter F1.05.
3.
Set the required operating pressure for stage 2 in parameter F1.06.
4.
Set the required operating pressure for stage 3 in parameter F1.07.
5.
Set the required operating pressure for stage 4 in parameter F1.08.
6.
Set the function of the digital inputs 15X1 at pin 7 and pin 8:
– Parameter F2.19 = 1 (pressure command value selection bit 0)
– Parameter F2.20 = 2 (pressure command value selection bit 1)
In "Premium" configuration, the pressure command value is defined via the
multi-Ethernet interface.
Commissioning
CytroPac, RE 51055-B/06.17, Bosch Rexroth AG