7.4 Water supply connection
For motor and frequency converter cooling, the hydraulic power unit must be
connected to a cooling water supply.
▶
Connect the lines to the intended cooling water ports, see fig. 12, pos. 1,
according to the circuit diagram.
▶
Tighten the fittings according to manufacturer specifications.
▶
Make sure that the cooling water supply temperature does not fall below the
dewpoint of the ambient air around the hydraulic power unit.
▶
Observe the following requirements:
– Maximum cooling water temperature: 25 °C.
– Minimum cooling water flow: 10 l/min.
– Maximum glycol content: 30 %.
1
Fig. 12: Cooling water ports
1
Cooling water ports 2 x G1/2