Power supply specifications

Table 36: Mains supply specifications
Operating voltage
Rated current (two- and four-zone control
panels)
110 VAC
240 VAC
Rated current (eight-zone control panels)
110 VAC
240 VAC
Voltage tolerance
Mains fuse
110 VAC
240 VAC
Table 37: 24 VDC power supply specifications
Two- and four-zone control panels
DC voltage
Rated current
Current range
Rated power
Voltage tolerance
Eight-zone control panel
DC voltage
Rated current
Current range
Rated power
Voltage tolerance
Table 38: Batteries and battery charger specifications
Batteries
Two- and four-zone control panels
Eight-zone control panel
Battery type
Battery charger voltage
Battery charger current
Two- and four-zone control panels
Eight-zone control panel
Out of service voltage level
No operation voltage level
SynaG Series Installation Manual
Chapter 5: Technical specifications
110 VAC / 60 Hz or 240 VAC / 50 Hz
2 A
2 A
3.15 A
1.5 A
+10% / −15%
T 3.15A 250V
T 2A 250V
24 V
2 A
0 to 2 A
50 W
±2%
24 V
4 A
0 to 4 A
100 W
±2%
2 x 7.2 Ah
2 x 7.2 Ah or 2 x 12 Ah
Sealed lead-acid
27.3 V at 20ºC −36mV/ºC
Max. 0.5 A
Max. 0.7 A
< 22.75 V
< 21 V