Connecting Supervised Outputs - UTC Fire and Security Kidde AirSense SynaG Series Installation Manual

Table of Contents

Advertisement

Chapter 2: Installation

Connecting supervised outputs

Control panels have the following supervised outputs:
Two-zone control panels have two outputs, marked OUT1 and OUT2.
Four- and eight-zone control panels have four outputs, marked OUT1, OUT2,
OUT3, and OUT4.
The outputs are supervised for open and short circuit faults.
Output class
The control panel outputs can be configured for Class A or Class B operation,
depending on the supervision mode required. The default output configuration is
Class B.
Table 11: Output classes and EN 54-13 supervision
Output class
EN 54-13 supervision
Class B (default)
Disabled
Class A
Enabled
For more information, see "EN 54-13 supervision mode" on page 34.
Output functionality
The function of each output is defined by the panel operating mode and output
class configuration (the default is Class B). All outputs are overload protected.
Table 12: Class B output functionality (default)
Operating mode
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
BS 5839-1
NBN S 21-100
NEN 2535
Table 13: Class A output functionality (for EN 54-13 compliance)
Operating mode
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
16
OUT1
OUT2
Sounders
Sounders
Sounders
Sounders
Sounders
Sounders
Sounders
Sounders
Evacuation
Evacuation
sounders
sounders
Sounders
Sounders
OUT1/OUT2
Sounders
Sounders
Sounders
Description
For installations not requiring EN 54-13
compliance
For installations requiring EN 54-13
compliance
OUT3
Sounders
Sounders
Sounders
Sounders
Warning
sounders
Fire routing
(automatic)
OUT3/OUT4
Fire routing
Sounders
Fire routing
SynaG Series Installation Manual
OUT4
Fire routing
Sounders
Fire routing
Sounders
Warning
sounders
Fire routing
(manual)

Advertisement

Table of Contents
loading

Related Products for UTC Fire and Security Kidde AirSense SynaG Series

Table of Contents