Fire Routing Delay - UTC Fire and Security Kidde AirSense SynaG Series Installation Manual

Table of Contents

Advertisement

Fire routing delay

Note:
Use this menu to configure warning sounder delays in NBN S 21-100
mode.
Use this menu to configure a fire routing delay of up to 10 minutes in operating
modes where the feature is available.
Default delays
The default fire routing delay for each operating mode is shown below.
Table 23: Default fire routing delay values
Operating mode
EN 54-2 Scandinavia
NEN 2535
EN 54-2
NBN S 21-100
EN 54-2 Evacuation
BS 5839-1
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes fast to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at Operator user level.
To enable a configured delay:
1. Exit Installer user level.
2. Enter the Operator user level password.
3. Press the Fire Routing Delay button.
A steady Fire Routing Delay LED indicates that the delay is enabled.
SynaG Series Installation Manual
Chapter 3: Configuration and commissioning
Default delay in minutes
01
01
00
This feature is not available in these operating modes.
37