Chapter 2: Installation
Note:
The default zone detection settings for each operating mode can be found
in Appendix A "Configuration presets" on page 79. To change the zone detection
setting, see "Advanced configuration" on page 39.

Connecting inputs

Input functionality
Each control panel has two inputs, marked INPUT1 and INPUT2. These circuits
are connected as normally open and activated when closed.
Both inputs are configurable (see "Input configuration" on page 47). The default
functionality of each input is defined by the panel operating mode and EN 54-13
configuration. See Table 7 below.
Table 7: Default input functionality for inputs 1 and 2
Operating mode
EN 54-2 [1]
EN 54-2 Evacuation [1]
EN 54-2 Scandinavia [1]
BS 5839-1 [1]
NBN S 21-100 [1]
NEN 2535 (EN 54-13 disabled) Fire routing inhibit delay
NEN 2535 (EN 54-13 enabled)
[1] No change to input functionality with EN 54-13 enabled.
[2] Remote reset for two-zone control panels operating in EN 54-2 Scandinavia mode.
[3] Supervised input (wiring short or open).
Connecting unsupervised inputs
Connect unsupervised input switches to INPUT1 and INPUT2, as shown in
Figure 4 or Figure 5 on page 11. Nominal resistance values (including any cable
resistance) are shown below.
Table 8: Nominal resistance values for unsupervised inputs
Input function
Remote reset command
Extended fire routing delay
Fire routing inhibit delay
Class change
Delays off
FBF (sounders disabled) [1]
[1] Regional fire brigade panels.
14
INPUT1
Remote reset
Remote reset
Extended fire routing delay [2]
Class change
Remote reset
Fire routing acknowledgement
(type 1, 100 seconds) [3]
Activated
> 9 kΩ to ≤ 9 kΩ
transition
≤ 9 kΩ
≤ 9 kΩ
≤ 9 kΩ
≤ 9 kΩ
≤ 9 kΩ
INPUT2
Delays off
Delays off
Delays off
Delays off
Delays off
Delays off
Fault warning output (open
supervision)
Standby
N/A
> 9 kΩ
> 9 kΩ
> 9 kΩ
> 9 kΩ
> 9 kΩ