Sounder operation during a zone test

Use this menu to configure the sounder operation during a zone test. The default
setting for all operating modes is ON.
To configure the sounder operation during a zone test:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes fast to indicate that the sounder
operation during a zone test configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
The internal buzzer and sounders sound for 5 seconds
when an alarm is activated in a zone test.
The internal buzzer and sounders do not sound when an
alarm is activated in a zone test.
42
Values
Read only
ON/OFF
N/A
N/A
N/A
Operating mode
All
All
All
All
All
All
SynaG Series Installation Manual