Chapter 3: Configuration and commissioning

Expansion board configuration

Expansion board labels
For configuration purposes expansion boards are labeled A and B (for two- and
four-zone control panels) or A, B, C, and D (for eight-zone control panels).
The label for a given module is defined by its position (left to right) in the control
panel cabinet, The first expansion board installed is module A, the second B, etc.
See your expansion board installation sheet for installation instructions.
Expansion board function and delay configuration
Once an expansion board is installed and added to the control panel
configuration, the following additional configuration options appear on the basic
and advanced configuration menus.
Note:
These configuration options are repeated for each of the installed
expansion boards (A, B, C, and D).
Table 27: Expansion board A configuration options
Display
Description
Module A function
Module A output 1 delay
Module A output 2 delay
Module A output 3 delay
Module A output 4 delay
[1] Available values depend on the type of expansion board installed and the supervision
selected. See Appendix A "Configuration presets" on page 79.
Expansion board function
Use this menu to configure the expansion board function. The default value
depends on panel configuration. For most configurations, the default value is 01.
For two-zone panels, or panels configured for EN 54-13, the default is 05. For the
available presets, see Appendix A "Configuration presets" on page 79.
To configure the expansion board function:
1. Set the display as shown below, and then press Enter.
52
Value
01 to 92 [1]
00 to 10 minutes
00 to 10 minutes
00 to 10 minutes
00 to 10 minutes
SynaG Series Installation Manual