Fire Alarm System Maintenance; Battery Maintenance - UTC Fire and Security Kidde AirSense SynaG Series Installation Manual

Table of Contents

Advertisement

Chapter 4: Maintenance

Fire alarm system maintenance

Perform the following maintenance tasks to ensure that the fire alarm system
works correctly and complies with all required European regulations.
Note:
Before performing any tests, ensure that fire routing (if configured) is
disabled or that the fire brigade has been notified.
Quarterly maintenance
Test at least one device per zone and verify that the control panel responds to all
fault and alarm events. The control panel power supply and battery voltage
should be checked.
Annual maintenance
Test all system devices and verify that the control panel responds to all fault and
alarm events. All electrical connections must be visually inspected to make sure
that they are securely fastened, that they have not been damaged, and that they
are appropriately protected.
Cleaning the control panel
Keep the outside and inside of the control panel clean. Carry out periodic
cleaning using a damp cloth for the outside. Do not use products containing
solvents to clean the control panel. Do not clean the inside of the cabinet with
liquid products.

Battery maintenance

Compatible batteries
The control panel requires two 12V, 7.2 or 12 Ah rechargeable sealed lead-acid
batteries. Compatible batteries for this product are shown in the table below.
Table 29: Compatible batteries
Model
Two- and four-zone control
panels
Eight-zone control panel
64
Battery type
12V, 7.2 Ah
12V, 7.2 Ah or 12V, 12 Ah
Recommended batteries
BS127N (7.2 Ah)
Fiamm FG20721/2 (7.2 Ah)
Yuasa NP7-12 (7.0 Ah)
BS127N (7.2 Ah)
BS130N (12 Ah)
Fiamm FG20721/2 (7.2 Ah)
Fiamm FG21201/2 (12 Ah)
Yuasa NP7-12 (7.0 Ah)
Yuasa NP12-12 (12 Ah)
SynaG Series Installation Manual