Battery startup
To power up the control panel from the batteries, press the battery start button on
the control panel PCB (marked as BAT. START, see Figure 20 below). Keep the
button pressed for approximately 5 seconds.
Figure 20: Battery startup button

Functional tests

Create a short and open circuit in the zone to test fault reporting for each.
Activate a manual call point to test manual alarm reporting. The control panel
should override any configured delays and activate alarm notification devices and
fire routing (where applicable) immediately.
Activate a detector to test automatic alarm reporting. The control panel should
initiate any configured delays and activate alarm notification devices and fire
routing (where applicable) once the delay time has elapsed.
Using a multimeter, verify that the fault relay is activated when a fault is reported
and that the alarm relay is activated when an alarm is reported.

Response times

Response times for standard events are as follows.
Table 28: Response times for standard events
Event
Alarm
Zone fault
Sounder fault
Fire routing fault
Expansion board fault
SynaG Series Installation Manual
Response time
Less than 3 seconds
Less than 30 seconds
Less than 30 seconds
Less than 30 seconds
Less than 100 seconds
Chapter 3: Configuration and commissioning
61