Sounder Re-Sound; Sounders Silence Disabled Time - UTC Fire and Security Kidde AirSense SynaG Series Installation Manual

Table of Contents

Advertisement

Sounder re-sound

Use this menu to configure the sounder re-sound, on or off. This determines
sounder operation in a fire alarm event when sounders have been silenced by
pressing the Sounder Start/Stop button and a new alarm event is reported. The
default setting is ON.
To configure the sounder re-sound:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes fast to indicate that the sounder re-
sound configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
The sounders re-sound if a new fire alarm event is
reported from a different zone.
The sounders do not re-sound if a new fire alarm event
is reported from a different zone.
Note: For new fire alarm events in the same zone, sounders will always re-
sound if the first alarm is reported by a detector and the new alarm is
reported by a manual call point.

Sounders silence disabled time

Note:
For control panels in basic evacuation mode, any configured fire sounders
silence disabled time is ignored.
To prevent the immediate silencing of sounders when a fire alarm is first
reported, the Sounder Start/Stop button may be temporarily disabled for a
preconfigured period of time when a configured sounder delay is counting down.
The disable time starts to count down when the control panel enters fire alarm
status and the configured sounder delay starts.
During the configured disable time the Sounder Start/Stop LED is off and the fire
sounders cannot be silenced (before activation) by pressing the Sounder
Start/Stop button.
SynaG Series Installation Manual
Chapter 3: Configuration and commissioning
43