4.3.1 Creating the Module

1
Add the MVI56E-MNETC module to the project.
In the Controller Organization window, select I/O C
the right mouse button to open a shortcut menu. On the shortcut menu,
choose N
EW
This action opens the Select Module dialog box.
2
Select the 1756-M
This action opens the New Module dialog box.
3
In the New Module dialog box, enter the following values.
Parameter
Name
Description
Comm Format
Slot
Input Assembly Instance
Input Size
Output Assembly Instance
Output Size
Configuration Assembly Instance
Configuration Size
Important: You must select the Comm Format as D
module will not communicate over the backplane of the ControlLogix rack.
Page 28 of 72
Modbus TCP/IP Multi Client Enhanced Communication Module
M
.
ODULE
(G
ODULE
ENERIC
Value
Enter a module identification string. Example: MNETC
Enter a description for the module. Example: M
M
ULTI
Select D
Enter the slot number in the rack where the MVI56E-MNETC
module is located.
1
250
2
248
4
0
MVI56E-MNETC ♦ ControlLogix Platform
ONFIGURATION
1756 M
) from the list and click OK.
ODULE
C
E
C
LIENT
NHANCED
OMMUNICATION
-INT.
ATA
- INT in the dialog box, otherwise the
ATA
and click
TCP/IP
ODBUS
M
ODULE
ProSoft Technology, Inc.
April 18, 2011