WAGO I/O-SYSTEM 750 Manual page 28

Fieldbus independent i/o modules 2 ao 0/+-10v dc 16 bit
Table of Contents

Advertisement

28 •
750-562 [2 AO 0/+-10V DC 16 Bit]
Parameter Setting
The following parameters can be changed and loaded onto the module.
Description
User Scaling
Offset
Gain
User Calibration
Offset
Gain
WAGO Calibration
Offset
Gain
* Factory setting
Input/Selection
Off*
On
0* ... +65535
0 ... 256* ... +65535
Off*
On
0 ... +65535
0 ... +65535
Active*
Deactivate user calibration to
activate
0 ... +65535
0 ... +65535
Description
Activation of the user scaling
Setting of the offset of the user
scaling
Setting of the amplification of the
user scaling
Switching on or off of the user
calibration.
If the user calibration is switched
off, the manufacturer calibration is
switched on automatically.
If the user calibration is switched
on, the manufacturer calibration is
switched off automatically.
Setting of the offset of the user
calibration
Setting of the amplification of the
user calibration
Switching on and of of the
manufacturer calibration.
If the user calibration is switched
off, the manufacturer calibration is
active automatically.
If the user calibration is switched
on, the manufacturer calibration is
switched off automatically.
Setting of the offset of the
manufacturer calibration
Setting of the amplification of the
manufacturer calibration
WAGO-I/O-SYSTEM 750
I/O Modules