WAGO I/O-SYSTEM 750 Manual page 18

Fieldbus independent i/o modules 2 ao 0/+-10v dc 16 bit
Table of Contents

Advertisement

18 •
750-562 [2 AO 0/+-10V DC 16 Bit]
Parameter Setting
Setting the numeric display (cf. register 32, bit 3, and bit 6)
Bit 6
Register
16 bit integer value with leading sign. The user scaling is activated or deactivated via bit 0 in
register 32.
Y
1
Register
16 bit fixed point value without leading sign. The user scaling is activated or deactivated via
bit 0 in register 32.
Y
1
Register
16 bit in X
The substitute value is placed on the output of the module after a system reset or an I/O
module timeout (module has received no process data for 100 ms).
The substitute value is selected via register 32, bit 9.
Register
16 bit integer value with leading sign.
The user calibration is active if bit 1 is not set in register 32.
Y
DAC
Bit 3
Display
0
X
0 ...65535
1
0
Twos complement
Leading
1
1
sign/amount
Function
33
User scaling offset
= X
* R34 / 256 + R33
IN
Function
34
User scaling gain
= X
* R34 / 256 + R33
IN
Function
35
User substitute value
coordinates, depending on the numeric format.
IN
Function
36
User calibration offset
= Y
* R37 / 8192 + R36
3
-10 V
0 V
0x0000
0x7FFF
0
32767
0x8000
0xFFFF
-32768
-1
0xFFFF
0x8001
-32767
-1
Memory
Access
RAM
R/W
Memory
Access
RAM
R/W
Memory
Access
RAM
R/W
Memory
Access
RAM
R/W
WAGO-I/O-SYSTEM 750
+10 V
10 V
0x8000
0xFFFF
32768
65535
0x0001
0x7FFF
0
32767
0x7FFF
0x0001
32767
Factory setting
0x0000
Factory setting
0x0100
Factory setting
MA: 0x0000
MB: 0x7FFF
Factory setting
0xXXXX
I/O Modules