WAGO I/O-SYSTEM 750 Manual page 16

Fieldbus independent i/o modules 2 ao 0/+-10v dc 16 bit
Table of Contents

Advertisement

16 •
750-562 [2 AO 0/+-10V DC 16 Bit]
Parameter Setting
Register
Bit 0: activation of the user scaling
0: *
1:
Bit 1: Activation of user calibration or manufacturer calibration
0:
1: *
Bit 2: Behavior of the RUN LEDs on I/O module timeout
0:
1: *
Bit 3: Process data display (cf. table "Setting the numeric display," see below)
0: *
1:
Bit 4, 5: Operating mode
Bit 6: Data format (cf. table "setting the numeric display," see below)
0: *
1:
Bit 7: Overrun limit
0: *
1:
Bit 8: Switch-on behavior
0: *
1:
Function
32
Mode setting
User scaling (register 33 and register 34) is not active.
User scaling (register 33 and register 34) is active.
User calibration (register 36 and register 37) is active.
Manufacturer calibration (register 18 and register 19) is active.
The RUN LED always lights up and the last output value is retained. On I/O module
timeout immediately after power up, 0 V is output. This is achieved by switching off
the scaling and calibration mechanisms and outputting values according to the
operating mode. This produces approximately 0 V with an imprecision in the lower
two-digit millivolt or microampere range.
The RUN LED goes out after 100 ms inactivity on the bus and the lower register 32
bit 10/11 configured reaction is carried out.
Takeover of the process data in 2 complement display (that is, -1 = 0xFFFF)
Takeover of the process data in amount/leading sign display (that is, -1 = 0x8001)
Bit 5
Bit 4
0
0
*
0
1
1
0
1
1
Data format 0 ... +65535
Data format -32768 ... 0 ... +32767
In case of exceeding or undershooting the limit values in register 42 (OVR) and
register 41 (UNR), only the corresponding bits are set in the status byte.
In case of exceeding or undershooting the limit values in register 42 (OVR) and
register 41 (UNR), only the corresponding bits are set in the status byte and the output
value is kept to the limit value.
Ready for operation in the configured operating mode
Outputs are high-ohm
Memory
EEPROM
Mode
Operating mode
EMPL
0 ... 10 V
MB
-10 V ... +10 V
MC
Not permissible, causes malfunctions!
MD
Not permissible, causes malfunctions!
Access
Factory setting
R/W
0x8006
WAGO-I/O-SYSTEM 750
I/O Modules