WAGO I/O-SYSTEM 750 Manual page 26

Fieldbus independent i/o modules 2 ao 0/+-10v dc 16 bit
Table of Contents

Advertisement

26 •
750-562 [2 AO 0/+-10V DC 16 Bit]
Parameter Setting
The following parameters can be changed and loaded onto the module.
Description
Operation Mode
Number Format
Output
Power-On Delay After
Excess Temperature
Shutdown
Keep Limit Values
Lower Limit Value
Upper Limit Value
K-Bus Timeout
Behaviour
Action at Timeout
Input/Selection
0 ... 10 V*
-10 ... +10 V
0 ... +65535*
-32768 ... +32767 (two´s
complement)
-32768 ... +32767 (sign and
magnitude)
Output process value*
Output high-impedance
0 ms
100 ms
200 ms
300 ms
500 ms*
750 ms
1 sec
2 sec
Off*
On
0* ... +65535
0 ... +65535*
Keep last output value
Execute the function below*
Output 0 V / 0 A*
Keep last value
Output high-impedance
User power-on value
WAGO power-on value
Description
Selection of the operating mode of
the device
Setting of the numeric display
Setting of the switch-on behavior
Setting of the switch-on delay
Setting of the overrun limitation
Setting of the lower limit value
underrange limit (UNR)
Setting of the upper limit value
overrange limit (OVR)
Behavior of the RUN LEDs on I/O
module timeout
RUN LED is always lit
Behavior of the RUN LEDs on I/O
module timeout
RUN LED goes out after 100 ms
Behavior after I/O module timeout
Substitute value after I/O module
timeout
WAGO-I/O-SYSTEM 750
I/O Modules

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-562