Wiring; General Wiring Guidelines; Operating Manual Pmcprotego S2-2(-C) - Pilz PMCprotego S2-2 Operating Manual

Safe motion
Table of Contents

Advertisement

Wiring

6
Wiring
6.1

General wiring guidelines

Inputs
}
Appropriate wiring must be used to exclude short circuits between the inputs or to a
supply line!
}
Signal lines must be shielded.
Outputs
}
If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load.
Possible remedy: Exclude the error by using separate multicore cable for supply
voltages
}
Use appropriate wiring to exclude short circuits between the outputs!
}
Signal lines must be shielded.
}
The outputs do not need suppression for inductive loads.
Cable material
}
Use copper wiring.
Please note:
}
Cable cross sections for field connection terminals in mm
}
Max. cable lengths

Operating Manual PMCprotego S2-2(-C)

1002529-EN-04
Digital inputs/outputs, supply voltage: 0.5 (AWG20),
crimp connectors with plastic collar in accordance with DIN 46228/4
2
0.5 mm
[H 0.5/16D] metrical. Ferrule length 10 mm, stripping length 12 mm
Supply voltage: Max. 30 m
Digital inputs and outputs: Max. 30 m
2
:
49