REVEXmax - User's Manual
7 Additional information
7.2.3

Setting information

Test leads compensation
The test leads' resistance is measured and then automatically memorized and sub-
tracted from Rpe measurement (see chapter 4.3.1).
Figure 27: Test leads compensation
Incorrect compensation for the test leads
If the measured value is less than the saved compensation value during measurement
(after subtraction, the memorized resistance will result in a negative number), the
display shows the absolute value and the symbol
on the display appears
CAL
inversely (Figure 28). In this case, it is necessary to perform the compensation
again (see chapter 4.3.1).
Figure 28: Incorrect compensation for the test leads
External input activation
After activation of the external input 10, a symbol is displayed (Figure 29). The
Test Socket 1 is not active.
Figure 29: External input activation
c 2019 ILLKO, s.r.o.
Page 54
www.illko.cz