Sensor Source Selections Submenu - Trane IntelliPak Signature Series Programming Manual

Commercial self-contained, 20/35-110ton
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

Programming SETUP
Water Economizer Min Position:
1.
Press the NEXT key until the following screen is displayed.
Select Water Flow Control Required For
Water Pump System:
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key until the following screen is displayed
Head Pressure Ctrl Setup Submenu
Press Enter to Review or Adjust
1.
Press the NEXT key until the following screen is displayed
Cond Temp Control Point:
1.
Press the NEXT key until the following screen is displayed
Preset Value to Min if Cond Water Below
Head Press Value Preset Temp Limit:
1.
Press the NEXT key until the following screen is displayed
Cond Temp Control Band
Lower Limit:
80 F
1.
Press the NEXT key until the following screen is displayed.
Cond Temp Control Band
Temporary Low Limit Suppression:
1.
Press the NEXT key until the following screen is displayed.
Cond Temp
Efficiency Check Point:
1.
Press the NEXT key until the following screen is displayed.
Cond Temp
Low Ambient Control Point:
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key to leave the submenu and show following screen.

Sensor Source Selections Submenu

Sensor Source Selections Submenu
Press ENTER to Review or Adjust
1.
Pressing the NEXT key will bypass this section.
26
10%
Variable/Minimize
90 F
90 F
Upper Limit: 120 F
10 F
105 F
90 F
Used With: Units with a waterside economizer
Possible Values: 0-100%
Used With: Water-cooled units with a
waterside economizer installed.
Possible Values: Constant/Maximize;
Variable/Minimize
Used With: All water-cooled units.
Possible Values: 80 - 100 F
Used With: All water-cooled units.
Possible Values: 80 - 100 F
Used With: All air-cooled units
Factory Presets: Upper: 120 F, Lower: 80 F
Possible Values: Lower: 70 F to 90 F, Upper:
110 F to 130 F
Used With: All air-cooled units
Factory Presets: 10 F
Possible Values: 0 to 20 F
Used With: All air-cooled units
Factory Presets: 105 F
Possible Values: 95 to 115 F
Used With: All air-cooled units
Factory Presets: 90 F
Possible Values: 80 F to 100 F
Used with: All Units.
PKG-SVP01E-EN

Advertisement

Table of Contents
loading

Table of Contents