Outside Air Ventilation Setup - Trane IntelliPak Signature Series Programming Manual

Commercial self-contained, 20/35-110ton
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

For Daytime Warmup Temp Crtl, Use sensor
Connected to: RTM ZONE TEMP INPUT
1.
Press the NEXT key until the following screen is displayed.
For Occupied Zone Temp Ctrl, Use Sensor
Connected To:
1.
Press the NEXT key until the following screen is displayed.
For Unoccupied Zone Temp Ctrl, Use Sensor
Connected To:
1.
Press the NEXT key until the following screen is displayed.
For Morning Warmup Temp Control, Use Sensor
Connected To:
1.
Press the NEXT key until the following screen is displayed.
For Zone Reset Function, Use Sensor
Connected To:
1.
Press the NEXT key until the following screen is displayed.
For Outside Air Preheat Ctrl, Use Sensor
Connected To:
1.
Press the NEXT key until the following screen is displayed.
Monitor Specific Temp Input, Use Sensor
Connected To:
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key to leave the submenu and show following screen.

Outside Air Ventilation Setup

Outside Air Ventilation Setup Submenu
Press ENTER to Review or Adjust
1.
Pressing the NEXT key will bypass this section.
PKG-SVP01E-EN
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
VCM MODULE AUX TEMP INPUT
RTM ZONE TEMP INPUT
Programming SETUP
Used With: Units with electric, Hydronic or
External Heat installed.
Possible Values: RTM ZONE TEMP INPUT, NSB
PANEL TEMP SENSOR INPUT, RTM AUX TEMP
INPUT, HEAT MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values: RTM ZONE TEMP INPUT, NSB
PANEL TEMP SENSOR INPUT, RTM AUX TEMP
INPUT, HEAT MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values: RTM ZONE TEMP INPUT, NSB
PANEL TEMP SENSOR INPUT, RTM AUX TEMP
INPUT, HEAT MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT
Used With: All Units when Electric, Hydronic or
External Heat is installed.
Factory Preset: RTM ZONE TEMP INPUT
Possible Values: RTM ZONE TEMP INPUT, NSB
PANEL TEMP SENSOR INPUT, RTM AUX TEMP
INPUT, HEAT MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT
Used With: All Units
Possible Values: RTM Zone Temp, NSB Panel
Temp Sensor Input, RTM Aux Temp Input, Heat
Module Aux Temp Input, ECEM Return Air Temp
Input
Used With: Units only when Traq™ Dampers
are installed
Possible Values: VCM Module Aux Temp Input;
WSM Mixed Air Temp Input
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values: RTM ZONE TEMP INPUT, NSB
PANEL TEMP SENSOR INPUT, RTM AUX TEMP
INPUT, HEAT MODULE AUX TEMP INPUT, ECEM
RETURN AIR TEMP INPUT, NO SENSOR
SELECTED
Used with: All Units when a VCM or airside
economizer is installed
27