Setpoint Menu - Trane IntelliPak Signature Series Programming Manual

Commercial self-contained, 20/35-110ton
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

SETPOINT Menu

The SETPOINT menu is used to designate default zone
temperature SETPOINTs, supply air and space pressure
SETPOINTs, and low ambient compressor lockout
SETPOINTs.
These SETPOINTs will be active (in use) for the "SETPOINT
Source Selection" designated as "DEFAULT" for these
inputs.
When a SETPOINT screen is displayed for 30 minutes
without a key being pressed, the LCD screen will revert to
the general operating status display. If this happens, press
the SETPOINT key again to return to the SETPOINT menu.
Note: Many of the screens displayed in this section are
applicable only for the options that are installed in
the unit and may not be visible on your unit.
Press the SETPOINT key to begin viewing or modifying the
unit SETPOINTs.
To change the sepoint values on a particular screen:
1. Press the plus or minus key until the correct value
appears in the screen.
Default Supply Air Temp SETPOINT
Cooling: 55 F
Default Supply Air Temp SETPOINTS
Cooling: 67 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temperature Deadband
Cooling: 8.0 F
Supply Air Temperature Deadband
Cooling: 8.0 F
1.
Press the NEXT key until the following screen is displayed.
Default Daytime Warmup SETPOINTS
Cooling: 67 F
1.
Press the NEXT key until the following screen is displayed.
Note: A minimum of 2° F is maintained between heating and cooling setpoints.
When Economizer Cooling, Reduce Zone
Temperature Cooling Setpoint By:
1.
Press the NEXT key until the following screen is displayed.
Default Unoccupied Zone Temp Setpoint(s)
Cool
1.
Press the NEXT key until the following screen is displayed.
36
Heating: 71 F
Heating: 4.0 F
Terminate: 71 F
85 F
2. Press the ENTER key to confirm your choice. If you've
made an error, press the CANCEL key to delete your
entry.
To navigate to another screen:
1. Press the NEXT key to advance to the next screen, or
a. if no further changes are required and you want to
exit back to view the unit operating status, press the
STATUS key once, or
b. if you want to remain in the Setpoint submenu,
press the SETPOINT key once and it will return you
to the beginning of that particular submenu, or
c. if you want to exit to another submenu in the in the
SEPOINT menu, press the SETPOINT key twice.
Then press the NEXT key to scroll through the
SETPOINT submenu choices, or
d. if you want to exit to another menu, such as
CONFIGURATION, press that key once, then press
the NEXT key toscroll through those screens.
1.5 F
Used With: All Units
Factory Presets: 55 F
Possible Values: 40 F to 90 F
Used With: All Units
Factory Presets: Heating: 100 F
Possible Values: Cool: 40 F to 90 F, Heat: 40
F to 180 F
Used With: All Units
Factory Presets: 8.0 F
Possible Values: Cooling: 4 - 20 F
Used With: All Units with hydronic heat
Factory Presets: Cooling: 8 F, heat: 4 F
Possible Values: Cooling:4 F to 20 F,
Heat: 2 F to 10 F
Used With: All units with Hydronic, Electric, or
External Heat installed.
Factory Presets: Heat = 71 F, Cool = 74 F
Possible Values:Heat = 50-90 F,
Cool = 52-92 F
Used With: All units with Hydronic Heat
installed.
Factory Presets: 1.5 F
Possible Values: 0.0-0.3 F
Used With: Cooling only units
Factory Presets: 85 F
Possible Values: Heat: 50 F to 90F
PKG-SVP01E-EN

Advertisement

Table of Contents
loading

Table of Contents