Programming SETUP
OA flow Compensation Function:
Use fixed OA Damper Minimum Position
1.
Press the NEXT key until the following screen is displayed.
OA Flow CO
Reset Function:
2
1.
Press the NEXT key until the following screen is displayed.
OA Flow CO
Reset Function:
2
CO
Start: 800 PPM
2
1.
Press the NEXT key until the following screen is displayed.
TRAQ Damper Quantity:
TRAQ Damper Size
1.
Press the NEXT key until the following screen is displayed.
OA Flow Calibration Data
Gain
1.0
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key to leave the submenu and show following screen.
Ventilation Override Definitions
Ventilation Override Definitions
Press ENTER to Review or Adjust
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
Supply Fan
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
Outside Air Dampers
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
Heat
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
VAV Box Relay
1.
Press the NEXT key until the following screen is displayed.
28
DISABLED
ENABLED
ENABLED
CO
Max:
1000 PPM
2
1
28 Inches
Offset
0.0 CCFM
Mode A
ON
Mode A
OPEN
Mode A
OFF
Mode A
DEENERGIZED
Used with: All Units when an airside
economizer and IGV or VFD is installed.
Possible Values: ENABLED, DISABLED
Enabled 2nd line= "OA Damper Min Pos
Depends on IGV/VFD Pos.; Disabled 2nd line=
"Use Fixed OA Damper Minimum Position"
Used with: Units with a VCM
Possible Values: ENABLED, DISABLED
Used with: Units with a VCM installed and CO
reset enabled.
Possible Values: ENABLED, DISABLED; CO2
Start = 0-1900 PPM; CO2 Max = 100-2000 PPM
Used with: All Units when an airside
economizer with a Traq™ damper installed.
Possible Values: Quantity = 1-12; Size = 0,
13, 16, 20, 24, or 28
Used with: Units with a VCM installed.
Factory Preset: Gain 1.0, Offset 0 CCFM
Possible Values: Gain= 0.5 to 1.5 (Default
1.0); Offset= -250 to 250 CCFM (Default 0 CFM)
Used with: All Units when VOM is installed
Used With: All Units when VOM and IGV or VFD
is installed
Factory Presets: Refer to Definitions
Possible Values: On, OFF
Used With: All Units when VOM and an airside
or waterside economizer is installed
Factory Presets: Refer to Definitions
Possible Values: OPEN/CLOSED
Used With: All Units when VOM and electric or
hydronic heat is installed
Factory Presets: Refer to Definitions
Possible Values: Off/In Control
Used With: Units with a VOM
Factory Presets: Refer to Definitions
Possible Values: ENERGIZED/DEENERGIZED