OPeRATOR PARAMeTeRS
Id-Text
os15
Meaning
Type
Data length
Access
Coding
Notice
Id-Text
os17
Meaning
Type
Data length
Access
Coding
Notice
Id-Text
os18
Meaning
Type
Data length
Access
Coding
Notice
Name
store mode
The memory type of non-volatile parameters must be adjusted
with this parameter. The parameters will not be stored if the val-
ue is "0", the device automatically changes to value "1" after the
next "power-down". This value is the default value, the non-vol-
atile parameters are always stored. Value „2" deactivates the
storing, also over the next start of the module.
Variable
8 bit
read / write
0: off, curr. off / on at startup
1: on, always store
2: off, never store
Standard value: 1
-
Name
safety type
Type of safety module
Variable
16 bit
read
0: no safety module available
1: Type 1 (STO)
Standard value: 0
-
Name
safety software date
Display of the software date of the safety module.
Variable
32 bit
read
0.0000...9999, 3112:
The year is displayed before the comma, month and day are
after that. 2012,0813 means 13.08.2012.If no safety module is
installed, the value "0: no safety functionality" is displayed.
Standard value: 0
-
Parameter index
0x208F
Parameter index
0x2091
Parameter index
0x2092