Integer Points - Process Technology LUFRAN Instruction

Fluoropolymer inline water heater
Table of Contents

Advertisement

OPTIONAL COMMUNICATIONS (Continued):

Integer Points:

The following table describes the standard integer points of the Lufran water heater.
These integer points are the same for both Ethernet (-C1) and DeviceNet (-C2)
communications
Integer
Data
Point
Inlet water
N48:01
temperature
(°C)
Outlet water
N48:02
temperature
(°C)
Flow rate
N48:03
(liters/min)
Heater
N48:04
output (%)
Set point
N48:05
(°C)
Remote
N48:07
control
System
N48:15
enabled
System
N48:16
operating
System at
N48:17
temperature
N48:18
System fault
N48:19
Error code
M-43-01
Revision - Date: 08 – 04/06/15
Signal
type
Heater
The value provided is the measured inlet water
output
temperature.
The value provided is the measured outlet water
Heater
temperature. This integer point may be used to monitor
output
the outlet temperature of the heater through the network.
Heater
The value provided is the measured water flow rate
output
through the heater.
Heater
The value provided is the current percentage (%) output
output
of the heating column(s).
The value provided is the outlet set point of the heater.
Heater
When the system is in REMOTE control mode, this value
output
should match integer point N50:11.
0 = System is in LOCAL control mode
Heater
1 = System is in REMOTE control mode
output
This setting is adjusted in the control access menu,
through the operator interface touch screen.
0 = System disabled
Heater
output
1 = System enabled
0 = Not operating
Heater
output
1 = Operating
0 = Outlet temperature is not within the process
deviation setting
Heater
output
1 = Outlet temperature is within the process deviation
setting
0 = No system fault detected
Heater
output
1 = System fault detected
The value provided will indicate which safety device has
Heater
tripped the system fault. For an explanation of a specific
output
error code, please consult the factory.
- 65 -
Description
Lufran Single Outlet Manual

Advertisement

Table of Contents
loading

Related Products for Process Technology LUFRAN