System Service Menu:

This menu provides buttons that can test the various output signals and indicator lights
on the unit, as well as shut down the OIP application software.
System Service Menu
Information Panel
TEST SONALERT
TEST RED STACK
LIGHT
TEST ALL REMOTE I/O
TEST AMBER STACK
LIGHT
SHUTDOWN
APPLICATION
TEST GREEN STACK
LIGHT
System Service Menu
Command Panel
APPLY
CANCEL
M-43-01
Revision - Date: 08 – 04/06/15
Figure 29: System Service Menu
Depress this button to energize the Sonalert audible alarm. This
function will not send the unit into an alarm condition.
Depress this button to illuminate the red light on the stack light.
This button allows testing of all output signals through the interface
cable. When this button is depressed, all interface outputs toggle
from normal operating states.
Depress this button to illuminate the amber light on the stack light.
When the heater is disabled, this button will shut down the OIP
application software. The PLC and the touch screen display will
remain turned on. When this button is depressed, a verification
message and two buttons in the command panel called APPLY and
CANCEL will appear.
Depress this button to illuminate the green light on the stack light.
This button will appear if the SHUTDOWN APPLICATION button is
depressed. Depress the APPLY button to shut down the DAC
control system.
This button will appear if the SHUTDOWN APPLICATION button is
depressed. Depress the CANCEL button return to the SYSTEM
SERVICE menu.
- 44 -