Alarms Menu - Process Technology LUFRAN Instruction

Fluoropolymer inline water heater
Table of Contents

Advertisement

Alarms Menu:

This menu provides a display status of all alarm conditions in the Lufran fluoropolymer
inline water heater. When one of the alarms trip, the Alarms menu will automatically
appear. The alarm setting(s) that has tripped will flash.
Note: To silence the audible alarm during an alarm event, press the POWER OFF
button on the front of the unit. When the alarm condition has been cleared,
press the POWER ON button before the unit is restarted.
When the alarm condition(s) has been corrected, the alarm setting will continue to flash
until the control system has been reset. To reset the safety, press the FAULT RESET
button located on the command panel.
Please note that the high-wattage Lufran heaters that use 3 or 4 heating columns
(157kW – 288kW) will have a slightly different alarm screen. Some of the alarms will be
multiplied due to the number of heating columns. These alarms will be labeled with the
column number.
Alarm Menu Command
Panel
FAULT RESET
Alarm Menu Navigation
Panel
ALARM HISTORY
M-43-01
Revision - Date: 08 – 04/06/15
Figure 32: Alarms Menu Screen
This button will reset all of the safety settings. If a particular safety
has tripped and the conditions causing the safety trip has not been
corrected, then the safety indicator will not reset and will continue to
flash.
This button will forward the operator to the ALARM HISTORY
display.
- 48 -