WARNING:
This document is a condensed reference. Read the safety instructions in your
information booklet before you begin.
NOTE:
The illustrations in this document are not intended to represent a specific switch.
NOTE:
Do not the use the mounted ReadyRails as a shelf or a workplace.

Rack mount safety considerations

Rack loading—Overloading or uneven loading of racks may result in shelf or rack failure, possibly damaging the equipment and causing
personal injury. Stabilize racks in a permanent location before loading begins. Mount the components starting at the bottom of the rack,
then work to the top. Do not exceed your rack's load rating.
Power considerations—Connect only to the power source specified on the unit. When you install multiple electrical components in a
rack, ensure that the total component power ratings do not exceed the circuit capabilities. Overloaded power sources and extension
cords present fire and shock hazards.
Elevated ambient temperature—If installed in a closed rack assembly, the operating temperature of the rack environment may be
greater than the room ambient temperature. Use care not to exceed the 45°C (113°F) maximum ambient temperature of the switch.
Reduced air flow—Install the equipment in the rack so that the amount of airflow required for safe operation of the equipment is not
compromised.
Reliable earthing—Maintain reliable earthing of rack-mounted equipment. Pay particular attention to the supply connections other than
the direct connections to the branch circuit, for example, use of power strips.
Do not mount the equipment with the back panel facing downward.

One-half U front-rack installation

Install the S5212F-ON switch using the following installation instructions.
NOTE:
To install the S5232F-ON, S5248F-ON, and S5224F-ON switches, see
S5296F-ON switch, see
The dual-tray mounting rails ship with the dual tray, not with the switch. You must supply eight rackmount screws for this installation.
To install the one-half U switch:
Attach the rails to the dual tray.
Install the dual tray in the four-post rack.
(Recommended) Attach the ground cable to the switch.
Install the switch in the dual tray.
NOTE:
Do not install the dual tray in a two-post rack.
1
Remove the dual tray and the rails from the shipping packaging and place them on a clean antistatic surface.
2
Line up the three holes on the inner switch rail with the dual-tray mounting heads.
3
Attach the rail to the dual tray. Slide the rail back until it locks into place.
32
S5200F-ON Series switch installation
Two U four-post rack
assembly.
Safety, Environmental, and Regulatory
One U ReadyRails
installation. To install the