Site Preparations; Site Selection; Cabinet Placement; Rack Mount - Dell EMC PowerSwitch Z9332F-ON Setup Manual

Hide thumbs Also See for PowerSwitch Z9332F-ON:
Table of Contents

Advertisement

The Z9332F-ON switch is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
Network telecommunication facilities
Data centers
Other locations where the National Electric Code (NEC) applies
For more information about the Z9332F-ON switch specifications, see Specifications.
NOTE:
Install the switch into a rack or cabinet before installing any additional components such as cables or optics.
Topics:

Site selection

Cabinet placement

Rack mount

Switch ground
Fans and airflow
Power
Storing components
Site selection
Install your equipment in restricted access areas. A restricted access area is one where service personnel can only gain access using a
special tool, lock, key, or other means of security. The authority responsible for the location controls access to the restricted area.
Ensure that the area where you install your switch meets the following safety requirements:
Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local electrical
codes.
Environmental—switch location—continuous temperature range is from 0°C to 45°C (32°F to 113°F).
Operating humidity is from 5 to 85 percent noncondensing, continuous.
In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot cooling vents or direct sunlight
Away from sources of severe electromagnetic noise
Positioned in a rack or cabinet, or on a desktop with adequate space in the front, back, and sides for proper ventilation and access
Install the switch in information technology rooms in accordance with Article 645 of the National Electrical Code and NFPA 75.
For more information about switch storage and environmental temperatures, see Specifications.
Cabinet placement
Install the Z9332F-ON switch only in indoor cabinets designed for use in a controlled environment.
Do not install the switch in outside cabinets. For cabinet placement requirements, see
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA) standard.
Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.
Rack mount
When you prepare your equipment rack, ensure that the rack is grounded. Ground the equipment rack to the same ground point the
power service in your area uses. The ground path must be permanent.