Home page – Add-on in function
17.4. ICONS DESCRIPTION
Icons
Description
Wood heating
Green: Heating mode
Yellow: Auxiliary
heating mode
Temperature in the
hot air plenum
17.5. LANGUAGE SELECTION, TEMPERATURE UNIT AND ALARM SOUND
To choose the language, the temperature unit and activate the alarm when the add-on is out of fire, press the
"Settings" button. In the "Main" menu, choose "SETUP" and then "GENERAL". Choose the preferred language, the
temperature unit and the alarm activation.
17.6. SYSTEM BALANCING
It is important to call upon a professional installer for the installation of the add-on and the ducting system
configuration. Certain check-ups must be performed and certain rules must be respected in order not to damage the
blower of the existing furnace.
When all components are installed on the add-on and the ducting system is connected to the various rooms of the
house, you must balance the ducting system. In order to do so, start the distribution blower of the existing furnace
select speed.
It is important to respect the velocity in the main duct, the secondary ducts, as well as the velocity at the room outlets.
The static pressure of your system must be adjusted to at least 0.2 IN.W.C. and must not exceed 0.5 IN.W.C. Finally,
make sure that you never exceed the maximum blower current of the existing furnace.
36
Icons
Description
Settings
Possible states of the add-on:
HEAT: When the word HEAT is green, the add-on is in heating mode.
If the add-on is waiting for a demand for heating, the word HEAT is
written in yellow.
OFF: The add-on is stopped.
Home page – Add-on off