7.5 CAN interface

CANopen is a communication profile for CAL-based industrial systems (refer to the CANopen CAL-Base
COMMUNICATION PROFILE for Industrial Systems; CiA 301 CANopen application layer and communication profile
Version: 4.2.0 21 February2011").
The ADP200 can be requested with the interface for connection to CAN networks at the time of ordering (ADP200-...-C
models). The CAN protocol (ISO 11898) used is CAN2.0A with 11-bit identifier. The integrated CANopen interface has
been developed as a Minimum Capability Device. Data are exchanged cyclically; the master reads the data made
available by the slaves and writes the reference data to the slaves.
The interface is provided with functional isolation (> 1 kV).
Connection is via the CAN (XC) connector and no power supply is required.
FWD
REV
EN
ILIM
CAN
Prg
Enter
Terminal
L
GND
H
CAN (green)
Off
Flashing
On
A shielded twin-pair (of the type described in the CANopen specifications) must be used for connection to the bus, and
must be laid separately from the power cables, at a distance of at least 20 cm. Cable shielding must be grounded at
the two ends. If the cable shielding is grounded at different points of the system, use equipotential connection cables to
reduce the current flow between the drive and the CANbus master.
Note!
(*) As regards terminations: the first and last termination on the network must have a 120 ohm resistor between pins L and H.
Termination on RC-ADP200A and RC-ADP200AS control card
As an alternative to an external resistance, the termination can be inserted by using jumper P3 (present only on models
ADP200-...-C).
With the jumper ON, the termination is inserted; with the jumper OFF, the termination is not inserted.
n=0
AL
CAN LED
Name
CAN�L
CAN�GND
CAN�H
LEDs
MASTER
CANopen
(*)
120 ohm
Figure 7.5.1: CANbus connection
Figure 7.5.2: Termination on RC-ADP200A and RC-ADP200AS regulation card
ADP200 • Quick installation guide - Specifications and connection
Function
CAN�L bus line (low dominant)
Ground / 0V / V-
CAN�H bus line (high dominant)
Stop
Pre-operational
Operational
ADP200
CAN (XC)
L
GND H
P3
CAN connector (XC)
L GND H
Cable cross-section
0.2 ... 2.5 mm
AWG 26 ... 12
Meaning
ADP200
CAN (XC)
L GND H
(*)
120 ohm
OFF
2
ON
43