Empty Pipe; Negative Flow Rate; Pulses - Tecfluid FLOMID Series Instruction Manual

Sensor, converter
Hide thumbs Also See for FLOMID Series:
Table of Contents

Advertisement

Example 1
If the output is programmed to activate at 100 m
flow rate is zero the output will be deactivated. When the flow rate reaches a value of 100
m
3
/h the output will be activated and it will not return to deactivated state until the level falls
below 90 m
3
/h.
Example 2
If the output is programmed to deactivate at 100 m
flow rate is zero the output will be activated. When the flow rate reaches a value of 100 m
the output will be deactivated and it will not return to activated state until the level falls below
90 m
3
/h.
7.5.2

Empty pipe

In this case, the output will change its status when the flowmeter detects empty pipe.
7.5.3
Negative flow rate
The output will change its status when the flow rate changes its sign.
7.5.4

Pulses

This option is only available on the digital 1. It allows to connect the converter to a PLC or
remote totalizer. The number of pulses per unit of volume can be programmed.
Note: The pulse output will be active only when the flow rate is positive. Otherwise, the
output will be permanently zero.
3
/h and to deactivate at 90 m
3
/h and to activate at 90 m
31
3
/h, when the
3
/h, when the
3
/h