7.5
Digital outputs (only with external power supply)
This screen allows to program the two digital outputs of the instrument.
By selecting one of the two outputs, the options for each of them appear on the next
screen.
7.5.1
Flow rate alarm
If Alarm is selected, the flow rate at which the outputs will change its status and the level of
hysteresis can be programmed. By level of hysteresis we understand the difference between
activation and deactivation of the output. To avoid that an alarm output is continuously
moving from activate to deactivate status, the points of activation and deactivation should
be programmed.
30