Record system 20 RED Series User Manual

Automatic door systems
Table of Contents

Advertisement

User manual record system 20 RED
automatic door systems - this is record!
Translation of the original manual

Advertisement

Table of Contents
loading

Summary of Contents for Record system 20 RED Series

  • Page 1 User manual record system 20 RED automatic door systems - this is record! Translation of the original manual...
  • Page 2: Table Of Contents

    Table of contents Table of contents Table of revisions ....................Safety instructions and regulations ..............Presentation of warning signs ......................General safety and accident prevention regulations..............Danger zones ..........................1.3.1 Security- and surveillance equipment .................... 1.3.2 Danger warnings on the product ....................1.3.3 Reconstructions and changes to the product.................
  • Page 3 Table of contents Manual opening and closing in case of failure (RED).......... Manual opening (without manual unlocking device) ..............Manual closing ..........................6.2.1 Step 1 ............................. 6.2.2 Step 2 ............................. Emergency opening of the door (RED) ............... Emergency opening with current supply ..................Emergency opening in case of power failure with auxiliary battery (RED) ........
  • Page 4: Table Of Revisions

    Table of revisions Table of revisions Document identification New chapter ..............9 Safety Instructions and Regulations Chapter Sequence Changed ......... 5 Use of the device Note according to IEC 60335-1 2010 changed ..... 6 BAL_SYS20_RED_EN_2V2_REC_102-020110693 4/ 27...
  • Page 5: Safety Instructions And Regulations

    Safety instructions and regulations Safety instructions and regulations Presentation of warning signs Various symbols are used in this guide for easier understanding: NOTICE Useful advice and information to ensure correct and efficient workflow of the system. IMPORTANT Specific details which are essential for trouble-free operation of the system. IMPORTANT Important details which must be read for proper function of the system.
  • Page 6: General Safety And Accident Prevention Regulations

    Safety instructions and regulations General safety and accident prevention regulations NOTICE This system is not intended to be used by persons (including children from the age of 8) with limited physical, sensory or mental abilities or with a lack of expe- rience and/or knowledge.
  • Page 7: Danger Zones

    Safety instructions and regulations CAUTION Unexpected OPENING / CLOSING / ROTATION • Bruises and contusions from the door wings/apron  No persons or objects are allowed in the opening area of the door.  No safety devices (sensors) should be removed or disabled. ...
  • Page 8: Intended Purpose Of Use

    Safety instructions and regulations Intended purpose of use The system is designed exclusively for use as a pedestrian passage. The installation may only occur in dry areas. If there are deviations then proper waterproofing and water drains will be required on- site.
  • Page 9: General Information

    General information General information Document identification Name: BAL_SYS20_RED_DE_2V2_REC_102-020110692 Version: V2.2 Article No.: 102-020110692 Date of publication: 03/2019 Application range STA/TSA 20RED/22RED NOTICE System 20 includes the following drives to which these instructions apply. STA/TSA 20 RED or 22 RED Target groups (User) This operating manual is intended for the target groups listed below: ▪...
  • Page 10: Maintenance And Regular Inspection

    General information Maintenance and regular inspection Prior to carrying out the first commissioning and if required as well as in accordance with the applica- ble regulations - however at least twice a year – a technical inspection by a skilled service technician or an authorized partner must take place.
  • Page 11 General information Function and safety Operator Monthly check Regular maintenance Technical expert 1 × per year, or accord- ing to country specific directives and regula- tions Regular testing (inspec- Technical expert 1 × per year, or accord- tion) ing to country specific directives and regula- tions Regular testing (inspec-...
  • Page 12: General Technical Data

    General technical data General technical data NOTICE Load capacity for lintel installations The standard guidelines for load capacities on lintel installations can be found in the corresponding chapter NOTICE 3 carriages required for door weight per wing > 90 kg 4 carriages required for door weight per wing >...
  • Page 13: Operating Instructions (Red)

    Operating instructions (RED) Operating instructions (RED) Selection of operating modes (RED) The electronic control unit BDE-D is a user-friendly input and output unit to control and customize (op- tional) the door operation. The LCD display with backlight gives information about the door status with symbols and clear text.
  • Page 14: Selection Of Special Functions (Red)

    Operating instructions (RED) NOTICE The reduced opening width is also effective with operating modes (One-Way) (Continuously open). Selection of special functions (RED) Function Display Description ▪ Door is closed and locked ▪ 1 keystroke unlocks the door ▪ An opening/closing cycle is performed Single opening ▪...
  • Page 15: Locking The Control Unit With A Key (Option)

    Operating instructions (RED) Locking the control unit with a key (option) IMPORTANT Standard EN 16005 requires protection, for the mode selection of operation of pedestrian automatic doors, used as emergency exits so that they may not be inadvertently locked when the building is in use. If a "locked"...
  • Page 16: Self-Test (Redundancy Test) Of Operator

    Self-test (redundancy test) of operator Self-test (redundancy test) of operator When a self-test is carried out? In certain conditions, the door automatically performs a so-called "redundancy test", i.e. the door car- ries out a slow opening and closing cycle, thereby checking safety functions. Such function is executed in particular in case of a change of the operating mode as specified below: ▪...
  • Page 17: Manual Opening And Closing In Case Of Failure (Red)

    Manual opening and closing in case of failure (RED) Manual opening and closing in case of failure (RED) Manual opening (without manual unlocking device) Initial situation: The door is disconnected from the mains and is blocked in the closed and locked position. ▪...
  • Page 18: Manual Closing

    Manual opening and closing in case of failure (RED) Manual closing Initial situation: Electric power is supplied. The door remains blocked in open position. NOTICE According to the kind of failure, the procedure for a manual closing will be differ- ent.
  • Page 19 Manual opening and closing in case of failure (RED) ▪ Besides, unscrew both accumulator (storage battery) fuses. ▪ The accumulator is located under the casing. ▪ Slide the door by hand into the closed posi- tion. ▪ Turn the unlocking lever clockwise and hold it in this position so that the door can close completely.
  • Page 20: Emergency Opening Of The Door (Red)

    Emergency opening of the door (RED) Emergency opening of the door (RED) Emergency opening with current supply By activating the emergency opening switch (optional), which must be placed beside the installation, the door will open as long as the operating mode Locked has not been selected. In this operating mode the door will remain locked.
  • Page 21: Closing And Locking The Door

    Emergency opening of the door (RED) 7.3.3 Closing and locking the door ▪ Activate the emergency opening ▪ This causes the locking device to be unlocked ▪ Slide the door manually into the closed position ▪ Keep the door leafs in the closed position ▪...
  • Page 22: Behaviour In Event Of Faults

    Behavior in event of faults Behavior in event of faults In the event of an irregularity or malfunction, different displays are shown depending on the control unit connected. NOTICE If the door performs a slow opening or closing movement, this can indicate a deliberate automatic redundancy test.
  • Page 23: Control Unit Bde-D Does Not React

    Behavior in event of faults Control unit BDE-D does not react If the control panel does not react when the keys are pressed or if no message appears on the dis- play, a reset of the control panel could eliminate the problem. Proceed as follows: RESET HARDWARE BDE-D Press E key >...
  • Page 24: Functions And Safety Check

    Functions and safety check Functions and safety check General remarks According to the legal provision in force, the operating entity of the automatic door is responsible for its maintenance and for the user's safety, as soon as the installation has been handed over. The regular inspection of single elements by the operator requires little time investment and reinforces the prevention of accidents caused by an inappropriate use of the door.
  • Page 25: Monthly Inspection Work To Be Carried Out By The Operating Company

    Functions and safety check Monthly inspection work to be carried out by the operating company The monthly inspection and maintenance of individual elements by the operating company requires little time and serves the reliable function, increased service life and operational safety of the system. Test / inspection Procedure Expected result...
  • Page 26 Functions and safety check Test / inspection Procedure Expected result ▪ Set the door to manual oper- ▪ The door leaf must be Continuous floor guide (instead ation (see chapter "Selecting properly guided of punctual door leaf guide) special functions") ▪...
  • Page 27: Recommended And Planned Spare- And Wear Parts

    Recommended and planned spare- and wear parts Recommended and planned spare- and wear parts Spare part/Wear part Interval * CO48 (Silicon or Rubber) 1 year * Pulley CO48 3 years Battery 3 years Antistatic brush 3 years Door leaf guide (plastic) 3 years Guiding pad 3 years...
  • Page 28 Contact ➔ record UK limited Head Office: Unit D, 9 Watt Place - Hamilton International Park - Blantyre - G72 0AH - UK Central Office: Batley Business Centre - Unit 40 - Annexe 2 - Technology Drive - Batley - Wf17 6ER - UK Southern Office: 17 Invincible Road - Farnborough - Gu14 7QU - UK tel.: +44 1698 376411 - fax: +44 1698 376422 -...

Table of Contents