4.4 NX4S1 Control Output Wiring

Relay 1 is defaulted for control of the Door 1 lock, Relay 2 is defaulted for the control
of the Door 2 lock, Relay 3 is defaulted for the control of the Door 3 lock, and Relay 4
is defaulted for the control of the Door 4 lock. Relays 5-8 are used as auxiliary relays.
Refer to the NetAXS™ Access Control Unit User's Guide for details on controlling the
relay operations.
Each relay also has a green indicator LED, which indicates the relay state. If the relay
is active, the LED is illuminated.
Power for the door locks or auxiliary loads must be supplied from a separate external
power supply.
A UL-listed system's power supply must also be UL-listed for this application.
Caution:
cable shield should be grounded at the panel only. Grounding at both ends can cause
ground loops which can be disruptive. Do not bundle these wires with
communication, reader, or supervised input wiring.
To minimize premature contract failure and increase system reliability, a contact
protection circuit (HAS part number S-4) is highly recommended. Locate the
protection circuit as close as possible to the load.

4.5 Communications

Caution:
Because UL has reviewed the NetAXS™ panel only as a standalone system, the
Note:
computer terminal, NetAXS™ gateway panel, and N-485_PCI-2 adapter appear in this
section's figures only to illustrate the installation and programming of the NetAXS™
panel.

RS-232 Communications

The NetAXS™ panel communicates with a PC through a 50-foot RS-232 cable (HAS
part number CBL50). Connect the RJ45 end of the cable to the jack on the NetAXS™
panel.
The cable is used to provide communication to a single panel. A second cable can be
used with another NetAXS™ control panel connected to a second COM
(communication) port, which would enable eight readers to be used, see
RS-232
communications.
16
www.honeywell.com
The cable shield should be grounded only at the panel earth ground.
The system has not been verified for compliance with UL1076 Burglar
The cable used must be sized for the current load and should be shielded. The
Do not route communication wires with power or locking devices.
Configuration. A USB converter is also available that will provide RS-232
Figure 9,