How to carry out a display test

You can test the message display and the indicators
on the control panel.
a.
Press the MENU ON/OFF key and then the F4
key to select [Test/Eng].
b.
Press the F1 key to select [Disp Test]. Check
that the following things happen: The display
clears, all the indicators illuminate, the display
blanks and each pixel of the display is tested,
the zonal indicators are illuminated odd then
even numbers are lit, the buzzer sounds two
distinct tones and then the display shows the
system status message. The display test lasts
for 4 seconds.
Vigilon

How to change your PIN code

"
The terms Password, PIN,
Usercode and Access code are used
interchangeably and mean the same.
A user PIN code is normally set up by the servicing
organisation during commissioning of the fire alarm
system. The customer PIN code (password) is set up
is for the end user. The person responsible for the fire
alarm system should be aware of this PIN code. For
security the PIN should be changed on a regular
basis. A previously created PIN can be changed by:
a.
Press the MENU ON/OFF button.
b.
Press the F4 button to select [Test/Eng].
c.
Press the F4 button to select [UserCode]. Use
the keypad to input your existing access code
and then press the Enter button.
d.
Press the F4 key to select <etc>, repeat until
[NewPass] is displayed.
e.
Press the F1 button to select [New Pass].
Notice a message on the display 'Enter new
access code' with a flashing cursor above it.
Use the keypad to input a PIN code and then
press the Enter button. Notice 'New access
code set up' appears on the display.
"
Any changes made to the PIN
code at the Control panel must be
backed-up to the panel memory. If this is
not done then the previous PIN is restored
on resetting the panel, see section on How
to save changes to memory.
It is not necessary to backup the
password held at a repeat panel.
COMPACT VOICE ALARM